Goodrive350A series high-performance multifunction VFD
Function parameter list
-207-
Function
code
Name
Description
Default
Modify
simple PLC
Code Binary
St
ACC/
DEC
T1
ACC/
DEC
T 2
ACC/
DEC
T3
ACC/
DEC
T4
BIT1
BIT0 0 00
01
10
11
BIT3
BIT2 1 00
01
10
11
BIT5
BIT4 2 00
01
10
11
BIT7
BIT6 3 00
01
10
11
BIT9
BIT8 4 00
01
10
11
BIT11 BIT10 5 00
01
10
11
BIT13 BIT12 6 00
01
10
11
BIT15 BIT14 7 00
01
10
11
BIT1
BIT0 8 00
01
10
11
BIT3
BIT2 9 00
01
10
11
BIT5
BIT4 10 00
01
10
11
BIT7
BIT6 11 00
01
10
11
BIT9
BIT8 12 00
01
10
11
BIT11 BIT10 13 00
01
10
11
BIT13 BIT12 14 00
01
10
11
BIT15 BIT14 15 00
01
10
11
Select corresponding
acceleration/deceleration time, and then
convert 16-bit binary number into
hexadecimal number, finally, and then set
corresponding function codes.
ACC/DEC time 1 is set by P00.11 and
P00.12; ACC/DEC time 2 is set by P08.00
and P08.01; ACC/DEC time 3 is set by
P08.02 and P08.03; Acceleration
/deceleration time 4 is set by P08.04 and
Setting range:0x0000
–0xFFFF
P10.36
PLC restart mode
0: Restart from the first step, namely if the
VFD stops during running (caused by stop
command, fault or power down), it will run
from the first step after restart.
0
◎