Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-90-
Setting
Function
Description
28
AO1 from the programmable card
0
–1000
29
AO2 from the programmable card
0
–1000
30
Rotational speed
0
–Twice the motor rated synchronous
speed
31
Output torque (bipolar)
0
–Twice motor rated torque. A negative
value corresponds to 0.0% by default.
32
AI/AO temperature detection output
AO value of AI/AO temperature detection
33
–63
Reserved
Related parameter list:
Function
code
Name
Description
Default
HDO output type
0: Open collector high-speed pulse
output
1: Open collector output
0
AO1 output
0: Running frequency
1: Set frequency
2: Ramp reference frequency
3: Rotational speed (100% corresponds
to the speed corresponding to max.
output frequency)
4: Output current (100% corresponds to
twice the VFD rated current)
5: Output current (100% corresponds to
twice the motor rated current)
6: Output voltage (100% corresponds to
1.5 times the VFD rated voltage)
7: Output power (100% corresponds to
twice the motor rated power)
8: Set torque (100% corresponds to
twice the motor rated torque)
9: Output torque (Absolute value, 100%
corresponds to twice the motor rated
torque)
10: AI1 input
11: AI2 input
12: AI3 input
0
Reserved
0
HDO high-speed pulse
output
0