Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-89-
Setting
Function
Description
0.0% by default.
12
AI3 input
0
–10V/0–20mA
13
High-speed pulse HDIA input
0.00
–50.00kHz
14
Value 1 set through Modbus/Modbus TCP
communication
0
–1000
15
Value 2 set through Modbus/Modbus TCP
communication
0
–1000
16
Value 1 set through
PROFIBUS/CANopen/DeviceNet
communication
0
–1000
17
Value 2 set through
PROFIBUS/CANopen/DeviceNet
communication
0
–1000
18
Value 1 set through Ethernet
communication
0
–1000
19
Value 2 set through Ethernet
communication
0
–1000
20
High-speed pulse HDIA input
0.00
–50.00kHz
21
Value 1 set through
EtherCAT/PROFINET/EtherNet IP
communication
0
–1000. A negative value corresponds to
0.0% by default.
22
Torque current (bipolar)
0
–Three times the motor rated current. A
negative value corresponds to 0.0% by
default.
23
Exciting current
0
–Three times the motor rated current. A
negative value corresponds to 0.0% by
default.
24
Set frequency (bipolar)
0
–Max. output frequency. A negative value
corresponds to 0.0% by default.
25
Ramp reference frequency (bipolar)
0
–Max. output frequency. A negative value
corresponds to 0.0% by default.
26
Rotational speed (bipolar)
0
–Synchronous speed corresponding to
max. output frequency A negative value
corresponds to 0.0% by default.
27
Value 2 set through
EtherCAT/PROFINET/EtherNet IP
communication
0
–1000