Goodrive350A series high-performance multifunction VFD
Function parameter list
-266-
Function
code
Name
Description
Default
value
Modify
P25.22
S10 switch-on
delay
0.000s
○
P25.23 S10 switch-off delay
0.000s
○
P25.24
AI3 lower limit
Used to define the relationship between the
analog input voltage and its corresponding
setting. When the analog input voltage
exceeds the range from the upper limit to the
lower limit, the upper limit or lower limit is
used.
When the analog input is current input,
0mA
–20mA current corresponds to 0V–10V
voltage.
In different applications, 100.0% of the analog
setting corresponds to different nominal
values. See the descriptions of each
application section for details.
The following figure illustrates the cases of
several settings:
-100%
100%
Corresponding
setting
AI
10V
20mA
0
AI3/AI4
Input filter time: to adjust the sensitivity of
analog input. Increasing the value properly
can enhance analog input anti-interference
but may reduce the sensitivity of analog input.
Note:
AI3 and AI4 can support
0
–10V/0–20mA input, when AI3 and AI4
select 0
–20mA input, the corresponding
voltage of 20mA is 10V.
Setting range of P25.24: 0.00V
0.00V
○
P25.25
Corresponding
setting of AI3 lower
limit
0.0%
○
P25.26
AI3 upper limit
10.00V
○
P25.27
Corresponding
setting of AI3 upper
limit
100.0%
○
P25.28 AI3 input filter time
0.030s
○
P25.29
AI4 lower limit
0.00V
○
P25.30
Corresponding
setting of AI4 lower
limit
0.0%
○
P25.31
AI4 upper limit
10.00V
○
P25.32
Corresponding
setting of AI4 upper
limit
100.0%
○
P25.33 AI4 input filter time
0.030s
○