Goodrive350A series high-performance multifunction VFD
Communication
-329-
Function
Address
Data description
R/W
Bit8: =0: Speed control =1: Torque control
Bit9: =0: Non position control
=1: Position control
Bit11
–Bit10: =0: Vector 0 =1: Vector 1
=2: Closed-loop vector
=3: Space voltage vector
VFD fault code
2102H
See the description of fault types.
R
VFD identification
code
2103H
GD350A-----0x01A2
R
Running frequency
3000H
0
–Fmax (Unit: 0.01Hz)
Compatible
with CHF100A
and
CHV100
communication
addresses
R
Set frequency
3001H
0
–Fmax (Unit: 0.01Hz)
R
Bus voltage
3002H
0.0
–2000.0V (Unit: 0.1V)
R
Output voltage
3003H
0
–1200V (Unit: 1V)
R
Output current
3004H
0.0
–3000.0A (Unit: 0.1A)
R
Rotating speed
3005H
0
–65535 (Unit: 1RPM)
R
Output power
3006H
-300.0
–300.0% (Unit: 0.1%)
R
Output torque
3007H
-250.0
–250.0% (Unit: 0.1%)
R
Closed-loop setting
3008H
-100.0
–100.0% (Unit: 0.1%)
R
Closed-loop feedback
3009H
-100.0
–100.0% (Unit: 0.1%)
R
Input state
300AH
000
–3F
Corresponding to the local HDIB/
HDIA/S4/S3/S2/S1
R
Output state
300BH
000
–0F
Corresponding
to
the
local
RO2/RO1/HDO/Y1
R
Analog input 1
300CH
0.00
–10.00V (Unit: 0.01V)
R
Analog input 2
300DH
0.00
–10.00V (Unit: 0.01V)
R
Analog input 3
300EH
-10.00
–10.00V (Unit: 0.01V)
R
Analog input 4
300FH
R