Goodrive350A series high-performance multifunction VFD
Function parameter list
-205-
Function
code
Name
Description
Default
Modify
P09.28
P10
—
Simple PLC and multi-step speed control
Function
code
Name
Description
Default
Modify
P10.00
Simple PLC mode
0: Stop after running once; the VFD stops
automatically after running for one cycle, and
it can be started only after receiving running
command.
1: Keep running in the final value after running
once; The VFD keeps the running frequency
and direction of the last section after a single
cycle.
2: Cyclic running; the VFD enters the next
cycle after completing one cycle until
receiving stop command and stops.
0
○
P10.01
Simple PLC
memory selection
0: No memory after power-off
1: Memory after power-off; PLC memories its
running stage and frequency before
power-off.
0
○
P10.02
Multi-step speed 0 Frequency setting range for steps from step 0
to step 15: -300.0
–300.0%. 100.0%
corresponds to the max. output frequency
P00.03.
Running time setting range for steps from
step 0 to step 15: 0.0
–6553.5s(min). The time
unit is specified by P10.37.
When simple PLC operation is selected, it is
required to set P10.02
the running frequency and running time of
each step.
Note:
The symbol of multi-step speed
determines the running direction of simple
PLC, and the negative value means reverse
running.
P10.02
P10.04
P10.06
P10.32
P10.30
P10.28
Deceleration time
(two steps)
Acceleration time
(two steps)
P10.03
P10.05
P10.07
P10.31
P10.33
When selecting multi-step speed running, the
multi-step speed is within the range of
-fmax
–fmax, and it can be set continuously.
0.0%
○
P10.03
Running time of
step 0
0.0s(min)
○
P10.04
Multi-step speed 1
0.0%
○
P10.05
Running time of
step 1
0.0s(min)
○
P10.06
Multi-step speed 2
0.0%
○
P10.07
Running time of
step 2
0.0s(min)
○
P10.08
Multi-step speed 3
0.0%
○
P10.09
Running time of
step 3
0.0s(min)
○
P10.10
Multi-step speed 4
0.0%
○
P10.11
Running time of
step 4
0.0s(min)
○
P10.12
Multi-step speed 5
0.0%
○
P10.13
Running time of
step 5
0.0s(min)
○