Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-72-
Ready
P00.01=0 (controlled by
keypad)
Motor type
(P02.00)
P02.00=1
P02.00=0
Input motor nameplate
(P02.12
–
P02.19)
Input motor nameplate
(P02.01
–
P02.05)
Complete parameter
rotary autotuning
Partial parameter rotary
autotuning
Set autotuning mode
Press "RUN" key to start
autotuning
Autotuning finished
Autotuning
Synchronous
motor
Asynchronous
motor
Complete parameter
static autotuning
Note:
Motor parameters must be set correctly according to the motor nameplate.
If rotary autotuning is selected during motor autotuning, disconnect the motor from the load to put
the motor in static and no-load state. Otherwise, the motor parameter autotuning results may be
incorrect. In addition, autotune
If static autotuning is selected for motor autotuning, there is no need to disconnect the motor from
the load, but the control performance may be impacted as only a part of the motor parameters
have been autotuned. In addition, autotune
can be obtained through calculation.
Motor autotuning can be carried out on the present motor only. If you need to perform autotuning
on the other motor, switch the motor through selecting the switchover channel of motor 1 and
motor 2 by setting the ones place of
Related parameter list: