Goodrive350A series high-performance multifunction VFD
Function parameter list
-226-
P15
—
Functions of communication expansion card 1
Function
code
Name
Description
Default
value
Modify
P15.00
Reserved
P15.01
Module address
0
–127
2
◎
P15.02
Received PZD2
0
–31
0: Invalid
1: Set frequency (0
–Fmax. Unit: 0.01Hz)
2: PID reference (-1000
–1000, in which 1000
corresponds to 100.0%)
3: PID feedback (-1000
–1000, in which 1000
corresponds to 100.0%)
4: Torque setting (-3000
–+3000, in which
1000 corresponds to 100.0% of the motor
rated current)
5: Setting of the upper limit of forward running
frequency (0
–Fmax. Unit: 0.01 Hz)
6: Setting of the upper limit of reverse running
frequency (0
–Fmax. Unit: 0.01 Hz)
7: Upper limit of electromotive torque
(0
–3000, in which 1000 corresponds to
100.0% of the motor rated current)
8: Upper limit of braking torque (0
–3000, in
which 1000 corresponds to 100% of the motor
rated current)
9: Virtual input terminal command (Range:
0x000
–0x3FF, corresponding to
S8/S7/S6/S5/HDIB/HDIA/S4/S3/S2/S1)
10: Virtual output terminal command (Range:
0x00
–0x0F, corresponding to
RO2/RO1/HDO/Y1)
11: Voltage setting (special for V/F separation)
(0
–1000, in which 1000 corresponds to
100% of the motor rated voltage)
12: AO1 output setting 1 (-1000
–+1000, in
which 1000 corresponds to 100.0%)
13: AO2 output setting 2 (-1000
–1000, in
which 1000 corresponds to 100.0%)
0
○
P15.03
Received PZD3
0
○
P15.04
Received PZD4
0
○
P15.05
Received PZD5
0
○
P15.06
Received PZD6
0
○
P15.07
Received PZD7
0
○
P15.08
Received PZD8
0
○
P15.09
Received PZD9
0
○
P15.10
Received PZD10
0
○
P15.11
Received PZD11
0
○
P15.12
Received PZD12
0
○