Goodrive350A series high-performance multifunction VFD
Function parameter list
-209-
Function
code
Name
Description
Default
Modify
Overvoltage stall
threshold
Output
frequency
Time t
Time t
DC bus voltage V
P11.04
Overvoltage stall
protection voltage
120
–150% (standard bus voltage) (380V)
136%
○
120
–150% (standard bus voltage) (220V)
120%
P11.05
Current limit
selection
During accelerated running, as the load is too
large, the actual acceleration rate of motor is
lower than that of output frequency, if no
measures are taken, the VFD may trip due to
overcurrent during acceleration.
0x00
–0x11
Ones place: Current limit action selection
0: Invalid
1: Always valid
Tens place: Hardware current limit overload
alarm selection
0: Valid
1: Invalid
0x01
◎
P11.06
Automatic current
limit level
Current limit protection function detects output
current during running, and compares it with
the current-limit level defined by P11.06, if it
exceeds the current-limit level, the VFD will
run at stable frequency during accelerated
running, or run in decreased frequency during
constant-speed running; if it exceeds the
current-limit level continuously, the VFD
output frequency will drop continuously until
reaching lower limit frequency. When the
output current is detected to be lower than the
current-limit level again, it will continue
accelerated running.
For G type:
160.0%
For P type:
120.0%
◎
P11.07
Frequency drop
rate during current
limit
10.00
Hz/s
◎