Goodrive350A series high-performance multifunction VFD
Function parameter list
-155-
Function
code
Name
Description
Default
Modify
slip compensation
coefficient of vector
control
Setting range: 50
–200%
P03.09
Current-loop
proportional
coefficient P
Note:
The two parameters are used to adjust
PI parameters of current loop; it affects
dynamic response speed and control
precision of the system directly. The default
value needs no adjustment under common
conditions.
Applicable to SVC mode 0 (P00.00=0),
SVC mode 1 (P00.00=1), and FVC mode
Setting range: 0
–65535
1000
○
P03.10
Current-loop
integral coefficient I
1000
○
P03.11
Torque setting
method
0
–1: Keypad (P03.12)
2: AI1
3: AI2
4: AI3
5: Pulse frequency HDIA
6: Multi-step torque
7: Modbus/Modbus TCP communication
8: PROFIBUS/CANopen/DeviceNet
communication
9: Ethernet communication
10: Pulse frequency HDIB
11: EtherCAT/PROFINET/EtherNet IP
communication
12: Programmable card
Note:
For these settings, 100% corresponds
to the motor rated current.
0
○
P03.12
Torque set through
keypad
-300.0%
–300.0% (of the motor rated current)
20.0%
○
P03.13
Torque reference
filter time
0.000
–10.000s
0.010s
○
P03.14
Setting source of
forward rotation
upper-limit
frequency in torque
0: Keypad (P03.16)
1: AI1
2: AI2
3: AI3
0
○