Goodrive350A series high-performance multifunction VFD
Installation guidelines
-25-
4.3.3 Wiring procedure of the main circuit terminals
1.
Connect the ground wire of the input power cable to the PE terminal of the VFD, connect the
3PH input cable to the R, S and T terminals, and tighten up.
2.
Connect the ground wire of the motor cable to the PE terminal of the VFD, connect the motor
3PH cable to the U, V and W terminals, and tighten up.
3.
Connect optional parts such as the braking resistor that carries cables to designated positions.
4.
Fasten all the cables outside the VFD mechanically if allowed.
The screw is
not fastened.
The screw is
fastened.
Figure 4.14 Screw installation diagram
4.4 Control circuit standard wiring
4.4.1 Basic control circuit wiring diagram
+24V
PE
COM
S4
S3
S2
S1
HDIB
PW
HDIA
Forward running
Forward jogging
Fault reset
+10V
AI1
AI2
GND
PE
-10V
(External)
VFD
AO1
V
I
SW2
GND
Analog output
0-10V/0-20mA
Y1
CME
COM
HDO
High-speed pulse output and open
collector output are available for
choice.
485+
485-
PE
RS485
communication
RO2C
RO2B
RO2A
RO1C
RO1B
RO1A
Relay 1 output
Relay 2 output
ON
OFF
SW3
Multi-function analog input
Power used for
frequency setting
H1
H2
+24V
S2
S1
Safety controller
Open
circuit
Safety input
Safety switch
Y1 output
Safety state
feedback
Figure 4.15 Control circuit wiring diagram