Goodrive350A series high-performance multifunction VFD
Function parameter list
-196-
Function
code
Name
Description
Default
Modify
consumption
braking threshold
voltage
consumption braking. Adjust this value
properly to achieve effective braking for the
load. The default value varies depending on
the voltage class.
Setting range: 200.0
–2000.0V
380.0V;
For 380V:
700.0V;
For 660V:
1120.0V
P08.39
Cooling-fan running
mode
0: Normal mode
1: Permanent running after power-on
2: Running mode 2
0
○
P08.40
PWM selection
0x0000
–0x1121
Ones place: PWM mode selection
0: PWM mode 1, 3PH modulation and 2PH
modulation
1: PWM mode 2, 3PH modulation
Tens place: PWM low-speed carrier limit
0: Low-speed carrier limit mode 1
1: Low-speed carrier limit mode 2
2: No limit
Hundreds place: Deadzone compensation
method
0: Compensation method 1
1: Compensation method 2
Thousands place: PWM loading mode
selection
0: Interruptive loading
1: Normal loading
0x1101
◎
P08.41
Overmodulation
selection
0x0000
–0x1111
Ones place: Whether to enable
overmodulation
0: Disable overmodulation
1: Enable overmodulation
Tens place: Overmodulation mode
0: Mild overmodulation
1: Deepened overmodulation
Hundreds: Carrier frequency limit
0: Yes
1: No
Thousands: Output voltage compensation
0: No
0x1001
◎