Goodrive350A series high-performance multifunction VFD
Function parameter list
-159-
Function
code
Name
Description
Default
Modify
P03.28
Static friction
compensation
coefficient
0.0
–100.0%
0.0%
○
P03.29
Corresponding
frequency point of
static friction
0.50Hz
1.00Hz
○
P03.30
High speed friction
compensation
coefficient
0.0
–100.0%
0.0%
○
P03.31
Corresponding
frequency of high
speed friction
torque
–400.00Hz
50.00Hz
○
P03.32
Enabling torque
control
0: Disable
1: Enable
0
◎
P03.33
Flux-weakening
integral gain
0
–8000
1200
○
P03.34
Flux-weakening
control mode
0x000
–0x112
Ones place: Control mode
0: Mode 0
1: Mode 1
2: Mode 2
Tens place: Compensation of inductance
saturation coefficient
0: Enable
1: Disable
Hundreds place: Reserved
0: Reserved
1: Reserved
0x000
●
P03.35
Control optimization
setting
0
–0x1111
Ones place: Torque command selection
0: Torque reference
1: Torque current reference
Tens place: Reserved
0: Reserved
1: Reserved
Hundreds place: indicates whether to enable
0x0000
○