Goodrive350A series high-performance multifunction VFD
Function parameter list
-144-
Function
code
Name
Description
Default
Modify
Restoring the default values may delete the
user password. Exercise caution when using
this function. The option 5 can be used only
for factory testing.
P01
—
Start and stop control
Function
code
Name
Description
Default
Modify
P01.00
Start mode
0: Direct start
1: Start after DC braking
2: Start after speedtracking
0
◎
P01.01
Starting frequency
of direct start
The parameter indicates the initial frequency
during VFD start. See P01.02 (Starting
frequency hold time) for detailed information.
Setting range: 0.00
–50.00Hz
0.50Hz
◎
P01.02
Starting frequency
hold time
Output frequency
fmax
t1
t
f1 set by P01.01
f1
t1 set by P01.02
Setting a proper starting frequency can
increase the torque during VFD start. During
the hold time of the starting frequency, the
output frequency of the VFD is the starting
frequency. And then, the VFD runs from the
starting frequency to the set frequency. If the
set frequency is lower than the starting
frequency, the VFD stops running and keeps
in the standby state. The starting frequency is
not limited in the lower limit frequency.
Setting range: 0.0
–50.0s
0.0s
◎
P01.03
Braking current
before start
The VFD performs DC braking with the
braking current before start and it speeds up
after the DC braking time. If the set DC
braking time is 0, DC braking is invalid.
Stronger braking current indicates larger
0.0%
◎
P01.04
Braking time before
start
0.00s
◎