Goodrive350A series high-performance multifunction VFD
Function parameter list
-235-
Function
code
Name
Description
Default
value
Modify
P17.01
Output frequency
Displays current output frequency of the VFD.
Range: 0.00Hz
0.00Hz
●
P17.02
Ramp reference
frequency
Displays current ramp reference frequency of
the VFD.
Range: 0.00Hz
0.00Hz
●
P17.03
Output voltage
Displays current output voltage of the VFD.
Range: 0
–1200V
0V
●
P17.04
Output current
Displays the valid value of current output
current of the VFD.
Range: 0.0
–5000.0A
0.0A
●
P17.05
Motor speed
Displays current motor speed.
Range: 0
–65535RPM
0 RPM
●
P17.06
Torque current
Displays current torque current of the VFD.
Range: -3000.0
–3000.0A
0.0A
●
P17.07
Exciting current
Displays current exciting current of the VFD.
Range: -3000.0
–3000.0A
0.0A
●
P17.08
Motor power
Displays current motor power; 100% relative
to rated motor power, positive value is
motoring state, negative value is generating
state.
Range: -300.0
–300.0% (relative to rated
motor power)
0.0%
●
P17.09 Motor output torque
Displays current output torque of the VFD;
100% relative to rated motor torque, during
forward running, positive value is motoring
state, negative value is generating state,
during reverse running, positive value is
generating state, negative value is motoring
state.
Range: -250.0
–250.0%
0.0%
●
P17.10
Estimated motor
frequency
Displays the estimated motor rotor frequency
under open-loop vector condition.
Range: 0.00
0.00Hz
●
P17.11
DC bus voltage
Displays current DC bus voltage of the VFD.
Range: 0.0
–2000.0V
0V
●
P17.12
Digital input
terminal state
Displays current digital input terminal state of
the VFD.
0x00
●