Goodrive350A series high-performance multifunction VFD
Function parameter list
-210-
Function
code
Name
Description
Default
Modify
Output current A
Output frequency f
Current-limit
threshold
Set
frequency
Acceleration
Constant
speed
Time t
Time t
Setting range of P11.06: 50.0
–200.0%
Setting range of P11.07: 0.00
–50.00Hz/s
P11.08
Pre-alarm selection
for VFD/motor
OL/UL
0x0000
–0x1134
Ones place:
0: Motor overload/underload pre-alarm,
relative to rated motor current.
1: VFD overload/underload pre-alarm, relative
to rated VFD current.
2: VFD output torque overload/underload
pre-alarm, relative to rated motor torque
3: Motor overload/underload pre-alarm. The
overload is relative to the motor rated current;
while the underload is relative to the motor
rated power.
4: VFD overload/underload pre-alarm. The
overload is relative to the VFD rated current;
while the underload is relative to the VFD
rated power.
Tens place:
0: The VFD continues running after
overload/underload alarm.
1: The VFD continues running after underload
alarm, and stops running after overload fault.
2: The VFD continues running after overload
alarm, and stops running after underload fault.
3: The VFD stops running after
overload/underload fault.
Hundreds place:
0: Always detect
1: Detect during constant-speed running
Thousands place: VFD overload current
0x0000
○