Goodrive350A series high-performance multifunction VFD
Function parameter list
-214-
Function
code
Name
Description
Default
Modify
over the VFD can be performed more quickly.
P11.26
Reserved
P11.27
VF vibration control
method
0x00
–0x11
Ones place:
0: Method 1
1: Method 2
Tens place:
0: Reserved
1: Reserved
0x00
◎
P11.28
SPO detection start
delay time
0.0
–60.0s
Note:
The SPO detection is started only after
the VFD runs for the delay time specified by
P11.28 to advoid false alarms caused by the
unstable frequency.
5.0s
○
P11.29
SPO unbalance
factor
0
–10
6
○
P11.30
Reserved
P11.31
Fault severity group
1
0x0000
–0x3333
Thousands place/Hundreds place/Tens
place/Ones place:
0: Report the fault
1: Report the fault after deceleration to stop
2: Pre-alarm, with the action executed
according to P11.51
3: Screen out the fault
Note
: Different fault actions are taken for
different fault severities. The first 10 faults are
not grouped by severity, but each four of the
subsequent faults are grouped by severity in
ascending order from right to left in
hexadecimal format, that is, from the ones
place to the thousands place (for example, the
ones place of fault severity group 1
corresponds to fault 11).
Group 1: Faults 11
–14 (OL1, OL2, SPI, SPO)
Group 2: Faults 15
–18 (OH1, OH2, EF, CE)
Group 3: Faults 19
–22 (ItE, tE, EEP, PIDE)
0x0000
○
P11.32
Fault severity group
2
0x0000
○
P11.33
Fault severity group
3
0x0000
○
P11.34
Fault severity group
4
0x0000
○
P11.35
Fault severity group
5
0x0000
○
P11.36
Fault severity group
6
0x0000
○
P11.37
Fault severity group
7
0x0000
○
P11.38
Fault severity group
8
0x0000
○
P11.39
Fault severity group
9
0x0000
○
P11.40
Fault severity group
10
0x0000
○