Goodrive350A series high-performance multifunction VFD
Function parameter list
-139-
password to enter the interface. (You are not advised to modify the factory parameters. Incorrect
parameter setting may cause operation exceptions or even damage to the VFD.) If password
protection is not in locked state, you can change the password any time. You can set P07.00 to 0 to
cancel the user password. When P07.00 is set to a non-zero value during power-on, parameters are
prevented from being modified by using the user password function. When you modify function
parameters through serial communication, the user password protection function is also applicable
and compliant with the same rule.
P00
—
Basic functions
Function
code
Name
Description
Default
Modify
P00.00 Speed control mode
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode
3: FVC
Note:
To select 0, 1, or 3 as the control mode,
enable the VFD to perform motor parameter
autotuning first.
2
◎
P00.01
Channel of running
commands
0: Keypad
1: Terminal
2: Communication
0
○
P00.02
Communication
mode of running
commands
0: Modbus/Modbus TCP
1: PROFIBUS/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/PROFINET/EtherNet IP
4: Programmable card
5: Wireless communication card
Note:
The options 1, 2, 3, 4, and 5 are add-on
functions and are available only when
corresponding expansion cards are
configured.
0
○
P00.03
Max. output
frequency
Used to set the max. output frequency of the
VFD. Pay attention to the function code
because it is the foundation of the frequency
setting and the speed of acceleration (ACC)
and deceleration (DEC)
Setting range: Max (P00.04
10.00)
–400.00Hz
50.00Hz
◎
P00.04
Upper limit of
running frequency
The upper limit of the running frequency is the
upper limit of the output frequency of the
50.00Hz
◎