Goodrive350A series high-performance multifunction VFD
Function parameter list
-186-
Function
code
Name
Description
Default
Modify
STOP/RST
STOP/RST is valid in any conditions.
0: Valid only for keypad control
1: Valid both for keypad and terminal control
2: Valid both for keypad and communication
control
3: Valid for all control modes
P07.05
–
P07.07
Reserved
P07.08
Frequency display
coefficient
0.01
–10.00
Display frequency = Running frequency *
1.00
○
P07.09
Rotational speed
display coefficient
0.1
–999.9%
Mechanical rotation speed = 120 * (Displayed
running frequency) *×P07.09/(Number of
motor pole pairs)
100.0%
○
P07.10
Linear speed
display coefficient
0.1
–999.9%
Linear speed = (Mechanical rotation speed) ×
1.0%
○
P07.11
Rectifier bridge
temperature
-20.0
–120.0°C
0.0°C
●
P07.12
Inverter
temperature
-20.0
–120.0°C
0.0°C
●
P07.13
Control board
software version
1.00
–655.35
Depends
on version
●
P07.14
Local accumulative
running time
0
–65535h
0h
●
P07.15
VFD electricity
consumption
high-order bits
Used to display the electricity consumption of
the VFD.
VFD electricity consumption =
Setting range of P07.15: 0
–65535 kWh
(*1000)
Setting range of P07.16: 0.0
–999.9 kWh
0kWh
●
P07.16
VFD electricity
consumption
low-order bits
0.0kWh
●
P07.17
VFD type
0x0000
–0xFFFF
Bit0
–Bit3: G type or P type
0: G type
0x1000
●