Goodrive350A series high-performance multifunction VFD
Function parameter list
-143-
Function
code
Name
Description
Default
Modify
P00.15
Motor parameter
autotuning
0: No operation
1: Rotary autotuning 1.
Comprehensive motor parameter autotuning.
It is recommended to use rotating autotuning
when high control accuracy is needed.
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in
cases where the motor cannot be
disconnected from load.
3: Static autotuning 2 (partial autotuning);
when the present motor is motor 1, only
P02.06, P02.07 and P02.08 are autotuned;
when the present motor is motor 2, only
P12.06, P12.07 and P12.08 are autotuned.
4: Rotary autotuning 2. Similar to rotary
autotuning 1, but it is valid only for AMs.
5: Static autotuning 3 (partial autotuning),
valid only for AMs.
0
◎
P00.16
AVR function
selection
0: Invalid
1: Valid during the whole procedure
The auto-adjusting function of the VFD can
eliminate the impact on the output voltage of
the VFD because of the bus voltage
fluctuation.
1
○
P00.17
VFD type
0: G type
1: P type
0
◎
P00.18
Function parameter
restore
0: No operation
1: Restore default values (excluding motor
parameters)
2: Clear fault records
3: Reserved
4: Reserved
5: Restore default values (for factory test
mode)
6: Restore default values (including motor
parameters)
Note:
After the selected operation is done,
this parameter is automatically restored to 0.
0
◎