Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-73-
Function
code
Name
Description
Default
Channel of running
commands
0: Keypad
1: Terminal
2: Communication
0
Motor parameter
autotuning
0: No operation
1: Rotary autotuning 1.
Comprehensive motor parameter
autotuning. It is recommended to use
rotating autotuning when high control
accuracy is needed.
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in
cases where the motor cannot be
disconnected from load.
3: Static autotuning 2 (partial autotuning);
when the present motor is motor 1, only
P02.06, P02.07 and P02.08 are autotuned;
when the present motor is motor 2, only
P12.06, P12.07 and P12.08 are autotuned.
4: Rotary autotuning 2. Similar to rotary
autotuning 1, but it is valid only for AMs.
5: Static autotuning 3 (partial autotuning),
valid only for AMs.
0
Type of motor 1
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
Rated power of AM 1 0.1
–3000.0kW
Model
depended
Rated frequency of
AM 1
0.01Hz
–P00.03 (Max. output frequency)
50.00Hz
Rated speed of AM 1 1
–60000rpm
Model
depended
Rated voltage of AM 1 0
–1200V
Model
depended
Rated current of AM 1 0.8
–6000.0A
Model
depended
Stator resistance of
AM 1
0.001
–65.535Ω
Model
depended
Rotor resistance of AM 0.001
–65.535Ω
Model