Goodrive350A series high-performance multifunction VFD
Function parameter list
-176-
Function
code
Name
Description
Default
Modify
P05.12 S1 switch-on delay
Used to specify the delay time corresponding
to the electrical level changes when the
programmable input terminals switch on or
switch off.
Si Electrical
level
Si Valid
Invalid
Switch-off delay
Switch-on delay
Invalid
Valid
Setting range: 0.000
–50.000s
Note:
After a virtual terminal is enabled, the
state of the terminal can be changed only in
communication mode. The communication
address is 0x200A.
0.000s
○
P05.13 S1 switch-off delay
0.000s
○
P05.14 S2 switch-on delay
0.000s
○
P05.15 S2 switch-off delay
0.000s
○
P05.16 S3 switch-on delay
0.000s
○
P05.17 S3 switch-off delay
0.000s
○
P05.18 S4 switch-on delay
0.000s
○
P05.19 S4 switch-off delay
0.000s
○
P05.20
HDIA switch-on
delay
0.000s
○
P05.21
HDIA switch-off
delay
0.000s
○
P05.22
HDIB switch-on
delay
0.000s
○
P05.23
HDIB switch-off
delay
0.000s
○
P05.24
AI1 lower limit
Used to define the relationship between the
analog input voltage and its corresponding
setting. When the analog input voltage
exceeds the range from the upper limit to the
lower limit, the upper limit or lower limit is
used.
When the analog input is current input,
0mA
–20mA current corresponds to 0V–10V
voltage.
In different applications, 100.0% of the analog
setting corresponds to different nominal
values. See the descriptions of each
0.00V
○
P05.25
Corresponding
setting of AI1 lower
limit
0.0%
○
P05.26
AI1 upper limit
10.00V
○
P05.27
Corresponding
setting of AI1 upper
limit
100.0%
○
P05.28 AI1 input filter time
0.030s
○
P05.29
AI2 lower limit
-10.00V
○