Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-71-
autotuning.
Although the motor does not run during static autotuning, the motor is still supplied
with power. Do not touch the motor during autotuning; otherwise, electric shock
may occur. Do not touch the motor before autotuning is completed.
If the motor has been connected to a load, do not carry out rotary autotuning.
Otherwise, the VFD may malfunction or may be damaged. If rotary autotuning is
carried out on a motor which has been connected to a load, incorrect motor
parameter settings and motor action exceptions may occur. Disconnect from the
load to carry out autotuning if necessary.
The VFD can drive both asynchronous motors and synchronous motors, and it supports two sets of
motor parameters, which can be switched over by multifunction digital input terminals or
communication modes.
Communication
(P00.01=2)
Terminal
(P00.01=1)
Keypad
(P00.01=0)
Modbus/
Modbus TCP
communication
PROFIBUS/
CANopen/
DeviceNet
communication
Start
Select running
command channel
(P00.01)
Switchover
channel for motor 1 and
motor 2
(P08.31)
Terminal function 35
Switch motor 1 to
motor 2
Communication set value
2009H
Motor 1
Motor 2
Invalid
Valid
BIT0
–
1=00
BIT0
–
1=01
P08.31 ones = 0
Ethernet
communication
P08.31 ones = 1
P08.31 ones = 2
P08.31ones = 3
EtherCAT/PROFINET/
EtherNet IP
communication
P08.31 ones = 4
The control performance of the VFD is based on accurate motor models. Therefore, you need to carry
out motor parameter autotuning before running a motor for the first time (taking motor 1 as an
example).