Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-49-
The running command channel can be set by terminal commands besides P00.01 and P00.02.
Current running
command channel
P00.01
Multi-function
terminal function (36)
Command switches
to keypad
Multi-function terminal
function (37)
Command switches to
terminal
Multi-function terminal
function (38)
Command switches to
communication
Keypad
/
Terminal
Communication
Terminal
Keypad
/
Communication
Communication
Keypad
Terminal
/
Note:
"/" means this multi-function terminal is invalid under current reference channel.
Related parameter list:
Function
code
Name
Description
Default
Speed control
mode
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode
3: FVC
Note:
To select 0, 1, or 3 as the control mode,
enable the VFD to perform motor parameter
autotuning first.
2
Channel of
running
commands
0: Keypad
1: Terminal
2: Communication
0
Communication
mode of running
commands
0: Modbus/Modbus TCP
1: PROFIBUS/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/PROFINET/EtherNet IP
4: Programmable card
5: Wireless communication card
0
Motor parameter
autotuning
0: No operation
1: Rotary autotuning.
Comprehensive motor parameter autotuning. It
is recommended to use rotating autotuning when
high control accuracy is needed.
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in cases
where the motor cannot be disconnected from
load.
3: Static autotuning 2 (partial autotuning); when
0