Goodrive350A series high-performance multifunction VFD
Function parameter list
-277-
Function
code
Name
Description
Default
value
Modify
P28.27
AI/AO detected
motor OH
pre-alarm threshold
0.0
–200.0°C
Note:
When the motor temperature exceeds
the value, the DO terminal with function 48 (AI
detected motor OH pre-alarm) outputs a valid
signal.
90.0°C
○
P90
—
Tension control in speed mode
Function
code
Name
Description
Default
Modify
P90.00
Tension control
mode
0: Invalid
1: Speed mode
2: Open-loop torque mode
3: Closed-loop torque mode
Note:
The value 0 indicates tension control is
invalid. Select a non-0 value to enable the
tension control function.
0
◎
P90.01
Winding/
unwinding mode
0: Winding
1: Unwinding
Note:
The motor forward rotation direction is
the winding direction. When using the tension
control mode, check whether the motor
rotation direction is correct in the winding
mode; if not, change the rotation direction by
swapping two phase wires of the motor. After
the rotation direction is corrected, the winding
mode can be switched to the unwinding mode
by setting P90.01 to 1 or changing the
winding/unwiding switchover terminals.
0
○
P90.02
Reel mechanical
transmission rate
0.01
–600.00
=Motor rotation speed/Reel rotation
speed=Reel diameter/Motor shaft diameter
1.00
○
P90.03
Max. linear speed 0.0
–6000.0 m/min
1000.0
m/min
○
P90.04
Input source of
linear speed
0: Keypad
1: AI1
2: AI2
3: AI3
4: High-speed pulse HDI
0
◎