Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-62-
Function
code
Name
Description
Default
Torque boost
cut-off of motor 1
0.0%
–50.0% (of the rated frequency of motor 1)
20.0%
V/F frequency
point 1 of motor 1
0.00Hz
0.00Hz
V/F voltage point 1
of motor 1
0.0%
–110.0%
0.0%
V/F frequency
point 2 of motor 1
0.00Hz
V/F voltage point 2
of motor 1
0.0%
–110.0%
0.0%
V/F frequency
point 3 of motor 1
0.00Hz
V/F voltage point 3
of motor 1
0.0%
–110.0%
0.0%
V/F slip
compensation gain
of motor 1
0.0
–200.0%
100.0%
Low-frequency
oscillation control
factor of motor 1
0
–100
10
High-frequency
oscillation control
factor of motor 1
0
–100
10
Oscillation control
threshold of motor
1
0.00Hz
–P00.03 (Max. output frequency)
30.00Hz
V/F curve setting of
motor 2
0: Straight-line V/F curve
1: Multi-point V/F curve
2: Torque-down V/F curve (power of 1.3)
3: Torque-down V/F curve (power of 1.7)
4: Torque-down V/F curve (power of 2.0)
5: Customized V/F curve (V/F separation)
0
Torque boost of
motor 2
0.0%: (automatic); 0.1%
–10.0%
0.0%
Torque boost
cut-off of motor 2
0.0%
–50.0%(of the rated frequency of motor 1)
20.0%
V/F frequency
0.00Hz
0.00Hz