Goodrive350A series high-performance multifunction VFD
Function parameter list
-273-
Function
code
Name
Description
Default
value
Modify
5: 60+48+60
6: 72+24+60
7: 84+24+60
8: 96+96+96
Tens place: Card that communicates with the
programmable card through PZD (valid only
when the ones place of P27.26 is 5)
0: DP card
1: CANopen card
2: PN card
Note: P27.26 can be changed at any time, but
the change will only take effect after the
re-power on.
P27.27
Programmable card
save function at
power failure
0
–1
0: Disable
1: Enable
1
◎
P28
—
Master/slave control functions
Function
code
Name
Description
Default
value
Modify
P28.00 Master/slave mode
0: Master/slave control is invalid
1: The local machine is a master
2: The local machine is a slave
0
◎
P28.01
Master/slave
communication
data selection
0: CAN
1: Reserved
0
◎
P28.02
Master/slave
control mode
0x000
–0x112
Ones place: Master/slave running mode
selection
0: Master/slave mode 0
(The master and slave adopt speed control
and maintain the power balance by droop
control)
1: Master/slave mode 1
(The master and slave must be in the same
type of vector control mode. The master is
speed control, and the slave will be forced to
be in the torque control mode.
0x001
◎