Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-75-
Function
code
Name
Description
Default
3: Switch over by Ethernet communication
4: Switch over by
EtherCAT/PROFINET/EtherNet IP
communication
Tens: Motor switchover during running
0: Disable switchover during running
1: Enable switchover during running
Type of motor 2
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
Rated power of AM 2 0.1
–3000.0kW
Model
depended
Rated frequency of
AM 2
0.01Hz
–P00.03 (Max. output frequency)
50.00Hz
Rated speed of AM 2 1
–60000rpm
Model
depended
Rated voltage of AM 2 0
–1200V
Model
depended
Rated current of AM 2 0.8
–6000.0A
Model
depended
Stator resistance of
AM 2
0.001
–65.535Ω
Model
depended
Rotor resistance of AM
2
0.001
–65.535Ω
Model
depended
Leakage inductance of
AM 2
0.1
–6553.5mH
Model
depended
Mutual inductance of
AM 2
0.1
–6553.5mH
Model
depended
No-load current of AM
2
0.1
–6553.5A
Model
depended
Rated power of SM 2 0.1
–3000.0kW
Model
depended
Rated frequency of
SM 2
0.01Hz
–P00.03 (Max. output frequency)
50.00Hz
Number of pole pairs
of SM 2
1
–50
2
Rated voltage of SM 2 0
–1200V
Model
depended