Goodrive350A series high-performance multifunction VFD
Function parameter list
-198-
Function
code
Name
Description
Default
Modify
during frequency adjusting through other
communication methods
0: Save the setting at power-off.
1: Clear the setting at power-off.
P08.48
Initial electricity
consumption
high-order bits
Used to set the initial electricity consumption.
Initial electricity consumption =P08.48*1000+
Setting range of P08.48: 0
–59999 kWh (k)
Setting range of P08.49: 0.0
–999.9 kWh
0kWh
○
P08.49
Initial electricity
consumption
low-order bits
0.0kWh
○
P08.50
Magnetic flux
braking
Used to enable magnetic flux braking.
0: Invalid
100
–150: A greater coefficient indicates
greater braking strength.
The VFD can quickly slow down the motor by
increasing the magnetic flux. The energy
generated by the motor during braking can be
transformed into heat energy by increasing
the magnetic flux.
The VFD monitors the state of the motor
continuously even during the magnetic flux
period. Magnetic flux braking can be used for
motor stop, as well as for motor rotation
speed change. The other advantages include:
Braking is performed immediately after the
stop command is given. The braking can be
started without waiting for magnetic flux
weakening.
The cooling is better. The current of the stator
other than the rotor increases during
magnetic flux braking, while the cooling of the
stator is more effective than the rotor.
0
○
P08.51
VFD input power
factor
Used to adjust the display value on the AC
input side.
0.00
–1.00
0.56
○
P08.52 STO lock selection
0: Lock upon STO alarm
Lock upon STO alarm indicates resetting is
required after state restoration if STO occurs.
0
○