Goodrive350A series high-performance multifunction VFD
Function parameter list
-145-
Function
code
Name
Description
Default
Modify
braking power. The DC braking current before
start is a percentage of the VFD rated current.
Setting range of P01.03: 0.0
–100.0%
Setting range of P01.04: 0.00
–50.00s
P01.05
ACC and DEC
mode
The parameter indicates the changing mode
of the frequency during start and running.
0: Linear type. The output frequency
increases or decreases linearly.
fmax
Output frequency f
t1
t2
Time t
1: S curve. The output frequency increases or
decreases according to the S curve.
The S curve is generally applied to elevators,
conveyors, and other application scenarios
where smoother start or stop is required.
Output frequency f
Time t
fmax
t1
t2
Note:
If mode 1 is selected, set P01.06,
P01.07, P01.27, and P01.28 accordingly.
0
◎
P01.06
Time of starting
segment of ACC S
curve
The curvature of S curve is determined by the
ACC range and ACC/DEC time.
Output frequency f
Time t
t1
t2
t3
t4
t1=P01.06
t2=P01.07
t3=P01.27
t4=P01.28
Setting range: 0.0
–50.0s
0.1s
◎
P01.07
Time of ending
segment of ACC S
curve
0.1s
◎
P01.08
Stop mode
0: Decelerate to stop. After a stop command
0
○