Goodrive350A series high-performance multifunction VFD
Function parameter list
-208-
Function
code
Name
Description
Default
Modify
1: Continue running from the step frequency
when interruption occurred, namely if the VFD
stops during running (caused by stop
command or fault), it will record the running
time of current step, and enters this step
automatically after restart, then continue
running at the frequency defined by this step
in the remaining time.
P10.37 Multi-step time unit
0: second; the running time of each step is
counted in seconds
1: minute; the running time of each step is
counted in minutes
0
◎
P11
—
Protection parameters
Function
code
Name
Description
Default
Modify
P11.00
Phase-loss
protection
0x000
–0x111
Ones place:
0: Disable software input phase loss
protection
1: Enable software input phase loss protection
Tens place:
0: Disable output phase loss protection
1: Enable output phase loss protection
Hundreds place:
0: Disable hardware input phase loss
protection
1: Enable hardware input phase loss
protection
0x110
○
P11.01
Frequency drop at
transient power-off
0: Disable
1: Enable
0
○
P11.02
Energy braking in
standby state
0: Enable
1: Disable
0
◎
P11.03
Overvoltage stall
protection
0: Disable
1: Enable
1
○