Goodrive350A series high-performance multifunction VFD
Function parameter list
-261-
Function
code
Name
Description
Default
value
Modify
P24.02 Encoder direction
0x000
–0x111
Ones: AB direction
0: Forward
1: Reverse
Tens: Z pulse direction (reserved)
0: Forward
1: Reverse
Hundreds: CD/UVW pole signal direction
0: Forward
1: Reverse
0x000
◎
P24.03
Detection time of
encoder offline fault
0.0
–10.0s
2.0s
○
P24.04
Detection time of
encoder reversal
fault
0.0
–100.0s
0.8s
○
P24.05
Filter times of
encoder detection
Setting range: 0x00
–0x99
Ones place: Low-speed filter time,
corresponds to 2^(0
–9)×125μs.
Tens place: High-speed filter times,
corresponds to 2^(0
–9)×125μs.
0x33
○
P24.06
Speed ratio
between encoder
mounting shaft and
motor
You need to set the function code when the
encoder is not installed on the motor shaft and
the drive ratio is not 1.
Setting range: 0.001
–65.535
1.000
○
P24.07
Control parameters
of SM
0x0000
–0xFFFF
Bit0: Enable/disable encoder input filter
0: No filter
1: Filter
Bit1: Encoder signal filter mode
0: Self-adaptive filter
1: Use P24.18 filter parameters
Bit2: Enable/disable encoder
frequency-division output filter
0: No filter
1: Filter
Bit3: Enable/disable pulse reference
frequency-division output filter
0: No filter
0x0003
○