Goodrive350A series high-performance multifunction VFD
Function parameter list
-211-
Function
code
Name
Description
Default
Modify
reference selection
0: Related to current calibration coefficient
1: Irrelated to current calibration coefficient
P11.09
Overload pre-alarm
detection level
If the VFD or motor output current is larger
than the overload pre-alarm detection level
(P11.09), and the duration exceeds the
overload pre-alarm detection time (P11.10),
overload pre-alarm signal will be outputted.
Y1,
RO1, RO2
Output current
Overload pre-alarm
threshold
Time t
Time t
Pre-alarm time t
Pre-alarm time t
Setting range of P11.09: P11.11
–200%
Setting range of P11.10: 0.1
–3600.0s
G type:
150%
P type:
120%
○
P11.10
Overload pre-alarm
detection time
1.0s
○
P11.11
Underload
pre-alarm detection
level
Underload pre-alarm signal will be outputted if
the output current of the VFD or motor is lower
than underload pre-alarm detection level
(P11.11), and the duration exceeds underload
pre-alarm detection time (P11.12).
Setting range of P11.11: 0
Setting range of P11.12: 0.1
–3600.0s
50%
○
P11.12
Underload
pre-alarm detection
time
1.0s
○
P11.13
Fault output
terminal action
upon fault occurring
Used to set the action of fault output terminals
at undervoltage and fault reset.
0x00
–0x11
Ones place:
0: Act at undervoltage
1: Do not act at undervoltage
Tens place:
0: Act at fault reset
0x00
○