Goodrive350A series high-performance multifunction VFD
Function parameter list
-181-
Function
code
Name
Description
Default
Modify
P06.05
Output terminal
polarity selection
Used to set the polarity of output terminals.
When a bit is 0, the input terminal is positive;
When a bit is 1, the input terminal is negative.
BIT3
BIT2
BIT1
BIT0
RO2
RO1
HDO
Y1
Setting range: 0x00
–0x0F
0x00
○
P06.06 Y1 switch-on delay
Used to specify the delay time corresponding
to the electrical level changes when the
programmable output terminals switch on or
switch off.
Y electric level
Y valid
Invalid
Switch on
delay
invalid
Valid
Switch off
delay
Setting range: 0.000
–50.000s
Note:
P06.08 and P06.09 are valid only when
0.000s
○
P06.07 Y1 switch-off delay
0.000s
○
P06.08
HDO switch-on
delay
0.000s
○
P06.09
HDO switch-off
delay
0.000s
○
P06.10
RO1 switch-on
delay
0.000s
○
P06.11
RO1 switch-off
delay
0.000s
○
P06.12
RO2 switch-on
delay
0.000s
○
P06.13
RO2 switch-off
delay
0.000s
○
P06.14
AO1 output
0: Running frequency
1: Set frequency
2: Ramp reference frequency
3: Rotational speed (100% corresponds to the
speed corresponding to max. output
frequency)
4: Output current (100% corresponds to twice
the VFD rated current)
5: Output current (100% corresponds to twice
the motor rated current)
6: Output voltage (100% corresponds to 1.5
times the VFD rated voltage)
7: Output power (100% corresponds to twice
the motor rated power)
8: Set torque (100% corresponds to twice the
0
○
P06.15
Reserved
P06.16
HDO high-speed
pulse output
0
○