Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-48-
Ensure all the terminals are fixed and tightened firmly.
Ensure the motor matches with the VFD power.
5.5.2 Common commissioning procedure
The common operation procedure is shown in the following (taking motor 1 as an example).
Start
Power up after confirming the
wiring is correct
Restore to default values
Set the motor parameters of
P02.01
–
P02.05 as per the
motor nameplate
Set the motor parameters of
P02.15
–
P02.19 as per the
motor nameplate
Press QUICK/JOG to jog
If the motor rotates in wrong
direction, power off and exchange
the motor wires of any two
phases, and power on again
Set autotuning mode
Complete parameter rotary
autotuning
Partial parameter rotary
autotuning
Start autotuning after pressing
RUN key, and stop after
autotuning is done
Set running frequency
Set speed running control
mode (P00.00)
SVC 1 (P00.00=0)
SVC 2 (P00.00=1)
SVPWM control mode
(P00.00=2)
Set vector control parameters
in P03 group
Set vector control parameters
in P03 group
Set V/F parameters in P04
group
Set start/stop control
parameters in P01 group
Run after a running command
is given
Stop after a stop command is
given
End
Set running command channel
(P00.01, P00.02)
Complete parameter static
autotuning
Set control parameters in P03
and P20 groups
Closed-loop control mode
(P00.00=3)
Asynchronous
motor
Synchronous
motor
Note: If fault occurred, rule out the fault cause according to "fault tracking".