Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-66-
Function
code
Name
Description
Default
1
Enabling IF mode
for AM 2
0: Disable
1: Enable
0
Current setting in
IF mode for AM 2
When IF control is adopted for AM 2, the
function code is used to set the output current.
The value is a percentage in relative to the
rated current of the motor.
Setting range: 0.0
–200.0%
120.0%
Proportional
coefficient in IF
mode for AM 2
proportional
coefficient
When IF control is adopted for AM 2, the
function code is used to set the proportional
coefficient of output current closed-loop control.
Setting range: 0
–5000
650
Integral coefficient
in IF mode for AM
2
When IF control is adopted for AM 2, the
function code is used to set the integral
coefficient of output current closed-loop control.
Setting range: 0
–5000
350
Starting frequency
point for switching
off IF mode for AM
2
0.00
–P04.51
10.00Hz
P04.50
End frequency
point for switching
off IF mode for AM
1
P04.44
–P00.03
25.00Hz
P04.51
End frequency
point for switching
off IF mode for AM
2
P04.49
– P00.03
25.00Hz
5.5.5 Torque control
The VFD supports torque control and speed control. Speed control aims to stabilize the speed to keep
the set speed consistent with the actual running speed, meanwhile, the max. load-carrying capacity is
restricted by the torque limit. Torque control aims to stabilize the torque to keep the set torque
consistent with the actual output torque, meanwhile, the output frequency is restricted by the upper
and lower limits.