Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-129-
In running
Fault occurred, and the
keypad displayed fault
code
Figure out the fault
cause based on the
fault code
Figure out the most possible
cause according to P07.33
–
P07.40
Run again
Proper running
Rule out
fault based on
corresponding
solutions
Consult us
Y
N
N
Y
Related parameter list:
Function
code
Name
Description
Default
Present fault type
0: No fault
1: Inverter unit U phase protection (OUt1)
2: Inverter unit V phase protection (OUt2)
3: Inverter unit W phase protection (OUt3)
4: Overcurrent during acceleration (OC1)
5: Overcurrent during deceleration (OC2)
6: Overcurrent during constant speed (OC3)
7: Overvoltage during acceleration (OV1)
8: Overvoltage during deceleration (OV2)
9: Overvoltage during constant speed (OV3)
10: Bus undervoltage fault (UV)
11: Motor overload (OL1)
12: VFD overload (OL2)
13: Phase loss on input side (SPI)
14: Phase loss on output side (SPO)
15: Rectifier module overheat (OH1)
16: Inverter module overheat (OH2)
17: External fault (EF)
18: Modbus/Modbus TCP communication
0
Last fault type
0
2nd-last fault type
0
3rd-last fault type
0
4th-last fault type
0
5th-last fault type
0