Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-88-
Function
code
Name
Description
Default
0: Voltage
1: Current
5.5.10 Analog output
The VFD provides one analog output terminal (supporting 0
–10V/0–20mA) and one high-speed pulse
output terminal. Analog output signals can be filtered separately, and the proportional relation can be
adjusted by setting the max. value, min. value, and the percentage of their corresponding output.
Analog output signals can output the motor speed, output frequency, output current, motor torque and
motor power at a certain proportion.
0
1
2
3
.
.
.
.
.
.
19
20
P06.14
P06.16
AO1
HDO
P06.17
P06.18
P06.19
P06.20
P06.27
P06.28
P06.29
P06.30
P06.21
P06.31
(Default value is 0)
(Default value is 0)
P06.00
(HDO output type)
0
1
P06.00
0: Open collector high-speed
pulse output
1: Open-collector output
Analog output curve setting
Analog output selection
Analog output filter
Terminal output is described as follows:
Setting
Function
Description
0
Running frequency
0
–Max. output frequency
1
Set frequency
0
–Max. output frequency
2
Ramp reference frequency
0
–Max. output frequency
3
Running speed
0
–Synchronous speed corresponding to
max. output frequency
4
Output current (relative to VFD)
0
–Twice the VFD rated current
5
Output current (relative to motor)
0
–Twice the motor rated current
6
Output voltage
0
–1.5 times the VFD rated voltage
7
Output power
0
–Twice the rated power
8
Set torque value (bipolar)
0
–Twice the VFD rated current. A negative
value corresponds to 0.0% by default.
9
Output torque (absolute value)
0
– +/-(Twice the motor rated torque)
10
AI1 input
0
–10V/0–20mA
11
AI2 input
0V
–10V. A negative value corresponds to