5.5.13 Simple PLC
Simple PLC is a multi-step speed generator, and the VFD can change the running frequency and
direction automatically based on the running time to fulfill process requirements. Previously, such
function was realized with external PLC, while now, the VFD itself can achieve this function.
The VFD can realize 16-step speeds control, and provide four groups of acceleration/deceleration
time for you to choose.
After the set PLC completes one cycle (or one segment), one ON signal can be output by the
multifunction relay.
Setup of running
parameters of
each PLC stage
Restart running
after the first
section
Continue running at
the frequency when
interruption
occurred
Stop after
running once
Keep running in the
final value after
running once
Cyclic running
0
1
2
P10.00
(
simple PLC mode
)
PLC mode
0
1
0
1
0
1
Normal running
P10.01 (simple PLC memory selection)
No memory
after power
off
Memory
after power
off
P10.36
(PLC restart mode)
P17.00
Power cut during
running
Terminal function 23
Simple PLC stop reset
Set frequency
Digital output 16
Simple PLC state completed
Digital output 17
Simple PLC cycle completed
Related parameter list:
Function
code
Name
Description
Default
Digital input function
selection
23: Simple PLC stop reset
24: Pause simple PLC
25: Pause PID control
Digital output function
selection
16: Simple PLC stage reached
17: Simple PLC cycle reached
Simple PLC mode
0: Stop after running once
1: Keep running in the final value after
running once
0