
51
Connecting MECHATROLINK Devices
Section 3-5
3-5-4
Counter Module, Pulse Output Module
Communications setting
For counter modules and pulse output modules, MECHATROLINK communi-
cations can be set using the DIP switches.
Transmission setting
MECHATROLINK communications can be specified using the DIP switches
(SW) 6 to 8.
See the table below.
Any change of the settings becomes valid after turning OFF the power once,
then ON again.
Station address setting
Station address can be set as shown in the table below using the DIP switch 1
to 5 (SW).
The bit 5 of SW specifies the number of 10s while the bit 1 to 4 of SW speci-
fies the number of units.
Do not change the setting while the power is being supplied.
Pin
Name
Setting
Content
Default setting
6
Baud rate
OFF
4 Mbps
OFF
ON
10 Mbps
7
Transmission bytes OFF
17 byte
OFF
ON
30 byte
8
Station address
OFF
Refer to Station
address setting
ON (Do not set to OFF.)
ON
SW
Station address
5
4
3
2
1
OFF
OFF
OFF
OFF
OFF
Do not set.
OFF
OFF
OFF
OFF
ON
1 (01H): Default setting
OFF
OFF
OFF
ON
OFF
2 (02H)
OFF
OFF
OFF
ON
ON
3 (03H)
to
to
OFF
ON
ON
ON
ON
15 (0FH)
ON
OFF
OFF
OFF
OFF
16 (10H)
ON
OFF
OFF
OFF
ON
17 (11H)
ON
OFF
OFF
ON
OFF
18 (12H)
ON
OFF
OFF
ON
ON
19 (13H)
to
to
ON
ON
ON
ON
ON
Do not set.
ON
OFF
1
2
3
4
5
6
7
8
SW (Default setting)
Summary of Contents for CS1W-MCH71 -
Page 2: ...CS1W MCH71 CJ1W MCH71 Motion Control Unit Operation Manual Revised June 2008 ...
Page 3: ...iv ...
Page 29: ...xxx ...
Page 33: ...xxxiv ...
Page 35: ...xxxvi ...
Page 39: ...xl ...
Page 69: ...24 Performance Section 1 7 ...
Page 99: ...54 Connecting MECHATROLINK Devices Section 3 5 ...
Page 283: ...238 Saving Data Section 5 4 ...
Page 417: ...372 Command Details Section 6 3 ...