Wiring
Control circuit specifications
FR-E700 SC EC/ENE
3 - 17
Output signals
Communication
Terminal
Name
Description
Rated
Specifications
Refer to
Page
Rela
y
A, B, C
Relay output
(alarm output)
The alarm is output via relay contacts. The block
diagram shows the normal operation and voltage
free status. If the protective function is activated,
the relay picks up.
Contact
capacity:
230 V AC/0.3 A
(Power factor:
0.4) or
30 V DC/0.3 A
Open c
ollec
tor
RUN
Inverter running
Switched low when the inverter output fre-
quency is equal to or higher than the starting fre-
quency (initial value 0.5 Hz).
Switched high during stop or DC injection brake
operation.
Permissible
load:
24 V DC (max.
27 V DC), 0.1 A
(A voltage drop
is 3.4 V maxi-
mum when the
signal is on.)
FU
Frequency
detection
The output is switched low once the output fre-
quency exceeds a value preset in Pr. 42 (or 43).
Otherwise the FU output is switched high.
SE
Open collector
output common
Reference potential for the signals RUN and FU.
This terminal is isolated from the reference poten-
tial of the control circuit SD.
—
—
Analog output
AM
Analog voltage out-
put
Select one e.g. output fre-
quency from monitor items.
The output signal is propor-
tional to the magnitude of the
corresponding monitoring
item.
Not output during inverter
reset.
Output item:
Output
frequency
(initial setting)
Output signal:
0–10 V DC
Permissible load
current:
1 mA
(load imped-
ance:
10 k
Resolution:
8 bit
Tab. 3-10:
Output signals
Name
Description
Specification
Refer to
Page
RS-485
PU connector
With the PU connector, communication can be
made through RS-485.
Conforming standard:
EIA-485 (RS-485)
Transmission format:
Multidrop
Communication speed:
4800 to 38400 bps
Overall length: 500 m
USB
USB connector
The FR Configurator can be operated by connect-
ing the inverter to the personal computer
through USB.
Interface: conforms to USB1.1
Transmission speed: 12 Mbps
Connector: USB mini B connec-
tor (receptacle mini B type)
Ethernet
Ethernet connector
Communication with network devices can be
made via Ethernet by connecting an Ethernet
cable to the Ethernet connector on the Ethernet
board.
Interface:
100BASE-TX/10BASE-T
Transmission speed:
10 or 100 Mbps
Connector: RJ45
Tab. 3-11:
Communication signals
B
C
A
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......