Parameter
Communication operation and setting
FR-E700 SC EC/ENE
6 - 279
●
Real-time monitor
Refer to section 6.11.2 for details of the monitor description.
햲
When Pr. 37 = "0.01 to 9998", displayed in integral number.
햳
Input terminal monitor details – MRS is OFF.
햴
Output terminal monitor details
햵
Details of option input terminal monitor 1 (input terminal status of FR-A7AX-Ekit-SC-E)
(All terminals are off when an option is not fitted.)
햶
Details of option input terminal monitor 2 (input terminal status of FR-A7AX-Ekit-SC-E)
(All terminals are off when an option is not fitted.)
햷
Details of option output terminal monitor (output terminal status of FR-A7AY-Ekit-SC-E/
FR-A7AR-Ekit-SC-E) (All terminals are off when an option is not fitted.)
Register
Description
Unit
Register
Description
Unit
40201
Output frequency/
speed
햲
0.01 Hz/1
40220
Cumulative
energizing time
1 h
40202
Output current
0.01 A
40223
Actual operation time
1 h
40203
Output voltage
0.1 V
40224
Motor load factor
0.1%
40205
Frequency setting/
speed setting
햲
0.01 Hz/1
40225
Cumulative power
1 kWh
40207
Motor torque
0.1%
40252
PID set point
0.1%
40208
Converter output
voltage
0.1 V
40253
PID measurement value
0.1%
40209
Regenerative brake duty
0.1%
40254
PID deviation value
0.1%
40210
Electronic thermal relay
function load factor
0.1%
40258
Option input terminal
status 1 d
—
40211
Output current peak
value
0.01 A
40259
Option input terminal
status 2
햶
—
40212
Converter output
voltage peak value
0.1 V
40260
Option output terminal
status
햷
—
40214
Output power
0.01 kW
40261
Motor thermal load factor
0.1%
40215
Input terminal status
햳
—
40262
Inverter thermal load
factor
0.1%
40216
Output terminal status
햴
—
40263
Cumulative power 2
0.01 kWh
Tab. 6-103:
Real-time monitor
b15
b0
—
—
—
—
—
RES
—
MRS
—
RH
RM
RL
—
—
STR
STF
b15
b0
—
—
—
—
—
—
—
—
—
—
ABC
FU
—
—
—
RUN
b15
b0
X15
X14
X13
X12
X11
X10
X9
X8
X7
X6
X5
X4
X3
X2
X1
X0
b15
b0
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
DY
b15
b0
—
—
—
—
—
—
RA3
RA2
RA1
Y6
Y5
Y4
Y3
Y2
Y1
Y0
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......