Parameter
Operation setting at alarm occurrence
FR-E700 SC EC/ENE
6 - 171
Using Pr. 65 you can select the alarm that will cause a retry to be executed. No retry will be made for
the alarm not indicated.
Alarm
Display
for Retry
Name
Parameter 65 Setting
0
1
2
3
4
5
E.OC1
Overcurrent shut-off during acceleration
✔
✔
—
✔
✔
✔
E.OC2
Overcurrent shut-off during constant speed
✔
✔
—
✔
✔
E.OC3
Overcurrent shut-off during deceleration or stop
✔
✔
—
✔
✔
✔
E.OV1
Regenerative overvoltage shut-off during acceleration
✔
—
✔
✔
✔
—
E.OV2
Regenerative overvoltage shut-off during constant speed
✔
—
✔
✔
✔
—
E.OV3
Regenerative overvoltage shut-off during deceleration or stop
✔
—
✔
✔
✔
—
E.THM
Motor overload shut-off (electronic thermal relay function)
✔
—
—
—
—
—
E.THT
Inverter overload shut-off (electronic thermal relay function)
✔
—
—
—
—
—
E.BE
Brake transistor alarm detection/Internal circuit error
✔
—
—
—
✔
—
E.GF
Output side earth (ground) fault overcurrent protection
✔
—
—
—
✔
—
E.USB
USB communication fault
✔
—
—
—
✔
—
E.OHT
External thermal relay operation
✔
—
—
—
—
—
E.OLT
Stall Prevention
✔
—
—
—
✔
—
E.OPT
Option fault
✔
—
—
—
✔
—
E.OP1
Communication option fault
✔
—
—
—
✔
—
E.PE
Parameter storage device alarm
✔
—
—
—
✔
—
E.MB4
Brake sequence fault
✔
—
—
—
✔
—
E.MB5
✔
—
—
—
✔
—
E.MB6
✔
—
—
—
✔
—
E.MB7
✔
—
—
—
✔
—
E.ILF
Input phase failure
✔
—
—
—
✔
—
Tab. 6-45:
Faults selected for retry
NOTES
When terminal assignment is changed using Pr. 190 to Pr. 192, the other functions may be
affected. Make setting after confirming the function of each terminal.
For a retry error, only the description of the first alarm is stored.
When an inverter alarm is reset by the retry function at the retry time, the accumulated data of the
electronic thermal relay function, regeneration converter duty etc. are not cleared. (Different from
the power-on reset.)
Retry is not performed if E.PE (Parameter storage device fault) occurred at power on.
If a fault that is not selected for a retry occurs during retry operation (retry waiting time), the retry
operation stops while the fault indication is still displayed.
E
CAUTION:
When you have selected the retry function, stay away from the motor and machine unless
required. They will start suddenly (after the reset time has elapsed) after occurrence of an alarm.
When you have selected the retry function, apply CAUTION seals in easily visible places.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......