Inspection
Maintenance and inspection
8 - 6
8.1.6 Cleaning
Always run the inverter in a clean status. When cleaning the inverter, gently wipe dirty areas with a soft
cloth immersed in neutral detergent or ethanol.
8.1.7
Replacement of parts
The inverter consists of many electronic parts such as semiconductor devices.
The following parts may deteriorate with age because of their structures or physical characteristics,
leading to reduced performance or fault of the inverter. For preventive maintenance, the parts must
be replaced periodically.
Use the life check function as a guidance of parts replacement.
햲
Replacement years for when the yearly average ambient temperature is 40 °C
(without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
햳
Output current: 80% of the inverter rated current
Cooling fan
The replacement interval of the cooling fan used for cooling the parts generating heat such as the
main circuit semiconductor is greatly affected by the ambient temperature. When unusual noise and/
or vibration is noticed during inspection, the cooling fan must be replaced immediately.
E
CAUTION:
Do not use solvent, such as acetone, benzene, toluene and alcohol, as they will cause the inverter
surface paint to peel off.
The display, etc. of the operation panel and parameter unit (FR-PU04/FR-PU07) are vulnerable
to detergent and alcohol. Therefore, avoid using them for cleaning.
Part Name
Standard Replacement Interval
햲
Description
Cooling fan
10 years
Replace (as required)
Main circuit smoothing capacitor
10 years
햳
Replace (as required)
On-board smoothing capacitor
10 years
Replace the board (as required)
Relays
—
As required
Tab. 8-4:
Wearing parts
NOTE
For parts replacement, consult the nearest Mitsubishi FA Centre.
NOTE
The FR-E720S-030SC or less and the FR-E740-026SC or less are not provided with a cooling fan.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......