Parameter
Misoperation prevention and parameter setting restriction
FR-E700 SC EC/ENE
6 - 197
6.17.3
Reverse rotation prevention selection (Pr. 78)
In some applications (fans, pumps) it is necessary to ensure that the motor cannot be reversed. This
can be achieved with Pr. 78.
The above parameter can be set when Pr. 160 "User group read selection" = 0.
Set this parameter when you want to limit the motor rotation to only one direction.
This parameter is valid for all of the reverse rotation and forward rotation keys of the operation panel
and parameter unit (FR-PU04/FR-PU07), the start signals (STF, STR signals) via external terminals, and
the forward and reverse rotation commands through communication.
Pr. No. Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
78
Reverse rotation prevention
selection
0
0
Both forward and reverse rotations allowed
—
1
Reverse rotation disabled
2
Forward rotation disallowed