Parameter
Monitor display and monitor output signals
FR-E700 SC EC/ENE
6 - 141
Monitor description list (Pr. 52)
●
Set the monitor to be displayed on the operation panel and parameter unit (FR-PU04/FR-PU07)
in Pr. 52 "DU/PU main display data selection".
●
Set the monitor to be output to the terminal AM (analog output (0 to 10 V DC voltage output)) in
Pr. 158 "AM terminal function selection".
Types of Monitor
Unit
Pr. 52
Pr. 158 (AM)
Setting
Terminal AM
Full Scale Value
Description
Opera-
tion
Panel
LED
PU Main
Monitor
Output frequency
0.01 Hz
0/100
1
Pr. 55
Displays the inverter output frequency.
Output current
0.01 A/0.1 A
0/100
2
Pr. 56
Displays the inverter output current
effective value.
Output voltage
0.1V
0/100
3
200 V class
400 V
Displays the inverter output voltage.
400 V class
800 V
Alarm display
—
0/100
—
—
Displays 8 past alarms individually.
Frequency setting
0.01 Hz
5
a
5
Pr. 55
Displays the set frequency.
Motor torque
0.1%
7
a
7
Rated torque of the
applied motor × 2
Displays the motor torque in % on the
assumption that the rated motor
torque is 100%.
(Displays 0% during V/F control)
Converter output voltage
0.1 V
8
a
8
200 V class
400 V
Displays the DC bus voltage value.
400 V class
800 V
Regenerative brake duty
0.1%
9
a
9
Pr. 70
Brake duty set in Pr. 30, Pr. 70
Electronic thermal relay
function load factor
0.1%
10
a
10
100%
Displays the motor thermal cumulative
value on the assumption that the ther-
mal operation level is 100%.
햷
Output current peak value
0.01 A
11
a
11
Pr. 56
Holds and displays the peak value of
the output power monitor.
(Cleared at every start)
Converter output voltage
peak value
0.1 V
12
a
12
200 V class
400 V
Holds and displays the peak value of
the DC bus voltage value.
(Cleared at every start)
400 V class
800 V
Output power
0.01 kW
14
a
14
Rated inverter
power × 2
Displays the power on the inverter out-
put side
Input terminal status
—
—
a
—
—
Displays the input terminal ON/OFF sta-
tus on the PU.
(Refer to page 6-145 for DU display.)
Output terminal status
—
a
—
—
Displays the output terminal ON/OFF
status on the PU.
(Refer to page 6-145 for DU display.)
Cumulative
energization time
햳
1 h
20
—
—
Adds up and displays the energization
time after inverter shipment.
You can check the numbers of the
monitor value exceeded 65535h with
Pr. 563.
Reference voltage output
—
—
21
—
Terminal AM: Output 10 V
Tab. 6-35:
Monitor description list (1)
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......