Parameter overview
Parameter
6 - 2
Func-
tion
Parameter
Name
Incre-
ments
Initial
Value
Setting
Range
Description
Para-
meter-
Copy
Para-
meter
Clear
All
Para-
meter
Clear
Refer
to
Page
Rela
te
d
Paramet
ers
✔
: Enabled
—: Disabled
Base fr
equenc
y, v
oltage
3
Base frequency
0.01 Hz
50Hz
0–400 Hz
Set the frequency when the motor rated
torque is generated. (50Hz/60Hz)
✔
✔
✔
19
Base frequency voltage
0.1 V
8888
0–1000 V
Maximum inverter output voltage
✔
✔
✔
8888
95% of power supply voltage
9999
Same as power supply voltage
47
Second V/F (base frequency)
0.01 Hz
9999
0–400 Hz
Set the base frequency when the RT signal is
on.
✔
✔
✔
9999
Second V/F is invalid.
Multi-speed setting oper
ation
4
Multi-speed setting
(high speed)
0.01 Hz
50Hz
0–400 Hz
Set frequency when the RH signal is on.
✔
✔
✔
5
Multi-speed setting
(middle speed)
0.01 Hz
30Hz
0–400 Hz
Set frequency when the RM signal is on.
✔
✔
✔
6
Multi-speed setting
(low speed)
0.01 Hz
10Hz
0–400 Hz
Set frequency when the RL signal is on.
✔
✔
✔
24
–
27
Multi-speed setting
4 speed to 7 speed
0.01 Hz
9999
0–400 Hz/
9999
Frequency from 4 speed to 15 speed can be
set according to the combination of the RH,
RM, RL and REX signals.
9999: not selected
✔
✔
✔
232
–
239
Multi-speed setting
8 speed to 15 speed
0.01 Hz
9999
0–400 Hz/
9999
✔
✔
✔
Tab. 6-1:
Parameter overview (2)
V/FV/FV/F
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......