Parameter
CC-Link IE Field Network Basic
FR-E700 SC EC/ENE
6 - 361
Instruction codes
Set the instruction code using a remote register (RWw) (Refer to page 6-358.)
The definition read by the instruction code is stored in the remote register (RWr). (Refer to page 6-359.)
Item
Read/
write
Instruc-
tion code
Description
Operation mode
Read
H7B
H0000:
Network operation mode
H0001:
External operation mode, External JOG operation mode
H0002:
PU operation mode, External/PU combined operation mode 1 and 2,
PUJOG operation mode
Write
HFB
H0000:
Network operation mode
H0001:
External operation mode
H0002:
PU operation mode (Pr. 79 = "6")
M
onit
or
Output fre-
quency/
speed
Read
H6F
H0000 to HFFFF
Output frequency: Increments 0.01 Hz
Machine speed: Increments 1 (When Pr. 37 "0")
Output
current
Read
H70
H0000 to HFFFF
Output current (hexadecimal): Increments 0.01 A
Output
voltage
Read
H71
H0000 to HFFFF
Output voltage (hexadecimal): Increments 0.1 V
Special
monitor
Read
H72
H0000 to HFFFF
Check the data of the monitor selected by the instruction code HF3.
Special
monitor
selection No.
Read
H73
H01 to HFF
Monitor selection data
(Refer to monitor code on page 6-363.)
Write
HF3
Faults
history
Read
H74 to
H77
H0000 to HFFFF: Last two fault records
For the data codes or details of fault records, refer to page 7-2.
Set frequency
(RAM)
Read
H6D
Read the set frequency/machine speed from the RAM or E²PROM.
H0000 to HFFFF:
Set frequency: 0.01Hz increments
Machine speed: 1 increments (When Pr. 37 "0")
Set frequency
(E²PROM)
H6E
Set frequency
(RAM)
Write
HED
Write the set frequency/machine speed into the RAM or E²PROM.
앫
H0000 to H9C40 (0 to 400.00Hz):
Frequency: 0.01Hz increments
앫
H0000 to H270E (0 to 9998):
Machine speed: 1 increments (When Pr. 37
"0")
앫
To change the set frequency consecutively, write data to the inverter RAM.
(Instruction code: HED)
Set frequency
(RAM and
E²PROM)
Write
HEE
Parameter
Read
H00 to
H63
앫
Refer to the instruction code in the appendix (page A-16) to read and write
as required.
Write to Pr. 77 and Pr. 79 is disabled.
When setting Pr.100 and later, set link parameter extended setting.
앫
Set 65520 (HFFF0) as a parameter value "8888" and 65535 (HFFFF) as "9999".
앫
When changing the parameter values frequently, set "1" in Pr. 342 to write
them to the RAM. (Refer to page 6-245)
Write
H80 to
HE3
Tab. 6-161:
Setting of the instruction codes and data (1)
b15
b8 b7
b0
H74
H75
H76
H77
Second fault in past
Latest fault
Fourth fault in past
Third fault in past
Sixth fault in past
Fifth fault in past
Eighth fault in past
Seventh fault in past
0
b15
(HA0)
(H30)
0 1 1 0 0 0 0
b8
1
b7
0 1 0 0 0 0 0
b0
Monitor example for faults history (instruction code H74)
Read data: H30A0
Second fault in past: THT
Latest fault: OPT
Second fault in past
Latest fault
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......