Frequency setting by external terminals
Parameter
6 - 62
Fig. 6-19:
Connection example
I001127E
NOTES
The priorities of the frequency commands by the external signals are "jog operation > multi-speed
operation > terminal 4 analog input > terminal 2 analog input". (Refer to section 6.16 for the fre-
quency command by analog input.)
Valid in external operation mode or PU/external combined operation mode (Pr. 79 = 3 or 4).
Multi-speed parameters can also be set in the PU or external operation mode.
Pr. 24 to Pr. 27 and Pr. 232 to Pr. 239 settings have no priority between them.
When a value other than "0" is set in Pr. 59 "Remote function selection", the RH, RM and RL signals
are used as the remote setting signals and the multi-speed setting becomes invalid.
The RH, RM, RL, REX signals can be assigned to the input terminal using any of Pr. 178 to Pr. 189
"Input terminal function selection". When terminal assignment is changed, the other functions
may be affected. Please make setting after confirming the function of each terminal.
Forward
rotation
Multi-speed
selec
tion
Fr
equenc
y setting
pot
entiomet
er