Parameter
Useful functions
FR-E700 SC EC/ENE
6 - 327
NOTES
Mask of data output and sampling of output current are not performed during acceleration/decel-
eration.
When the speed is changed to acceleration/deceleration from constant speed during start bit out-
put, the data is judged as invalid, the start bit is output as high pulse shape for 3.5 s, and the end
signal is output as low pulse shape for 16.5 s. The signal is output for at least 1 cycle even when
acceleration/deceleration state continues after the start bit output is completed.
When the output current value (inverter output current monitor) is 0 A on completion of the 1
cycle signal output, the signal is not output until the speed becomes constant next time.
The current average value monitor signal (Y93) is output as low pulse shape for 20 s (without data
output) under the following condition:
앫
When the motor is in the acceleration/deceleration state on completion of the 1 cycle signal
output.
앫
When 1-cycle signal output was ended during restart operation with the setting of automatic
restart after instantaneous power failure (Pr. 57
9999).
앫
When automatic restart operation was being performed with automatic restart after
instantaneous power failure selected (Pr. 57
9999) on completion of the data output mask.
When terminal assignment is changed using Pr. 190 to Pr. 192 "Output terminal function selec-
tion", the other functions may be affected. Please make setting after confirming the function of
each terminal.
The speed is changed to deceleration from the
constant speed during start bit output
Output frequency
Y93
Start bit
Output as high pulse shape
for 3.5 s
End signal
Output as low pulse shape for
16.5 s
Next cycle
Invalid cycle (20s)
Previous cycle
Time
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......